1500kw high voltage 3kv 6kv diesel generator with marathon alternator

1500kW High Voltage 3kV 6kV Diesel Generator with Marathon AlternatorGoogol High voltage series generator sets, power range is from 800kVA to 5000kVA, standard voltage or high voltage generating system. Alternator voltage: 3300V, 6300V, 10500V, 3600V, 6600V, 11000V, 13800VFrequency: 50Hz or 60HzSpeed: 1500rpm, 1800rpm, 1200

Featured Products

1500kw High Voltage 3kv 6kv Diesel Generator with Marathon Alternator

1500kW High Voltage 3kV 6kV Diesel Generator with Marathon Alternator

Googol High voltage series generator sets, power range is from 800kVA to 5000kVA, standard voltage or high voltage generating system.
 
Alternator voltage: 3300V, 6300V, 10500V, 3600V, 6600V, 11000V, 13800V
Frequency: 50Hz or 60Hz
Speed: 1500rpm, 1800rpm, 1200rpm, 1000rpm according to the engine brand

Performance Feature:
Engine and alternator shall be mounted on a same frame steel skid.
Small size, low weight, easy to operating, installation and maintenance.
Good Quality diesel engine.
World famous brand AC alternator: Stamford, Marathon, Leroy Somer, MVC, Engga.
Advanced and reliable control module: Key start, Auto start, Remote control by PC with RS232/485
Full range protect function and alarm shutdown feature.
Standard Control System: Deepsea 7320 AMF
Mains 3 phases VPh-N L1-N L2-N L3-N
Mains 3 phases VPh-pH L1-L2 L2-L3 L3-L1
Mains frequency Hz (L1)
Gen 3 phases VPh-N L1-N L2-N L3-N
Gen 3 phases VPh-pH L1-L2 L2-L3 L3-L1
Gen 3 phases current I1 I2 I3
Gen frequency Hz (L1)
Gen total apparent power ∑ A
Gen total active power ∑ P
Gen power factor PF (AV)
Genset speed RPM (signal from generator voltage frequency)
Engine oil pressure Bar (signal from engine P-sensor)
Engine coolant temperature (signal from engine T-sensor)
Battery voltage VDC
Genset Running hour Hour

Standard Accessory:
Common steel base frame, anti-vibrator, Exhaust silencer, Flexible pipe, Battery connecting wires, Operation manual and document.

Optional Accessory:
Circuit breaker, Starting Battery, Engine coolant and oil heater, Alternator space heater, Cooling for heat exchanger, Control system with RS232/485 communication interface, Battery charger by main supply, Fuel-water separator, Daily fuel tank, ATS and paralleling system, Soundproof Canopy and Moving Trailer.
Usage: Power plant, black start, emergency standby, large factory, data center, mining plant

Let's achieve our goal together, Using power to kindle the dream of human.
Engine Model QTA3240-G9-MV
Speed rpm1500
Frequency Hz50
 Rating Output  
Standby Output  ( LTP)kW*
Prime Output (PRP)kW1626 
Engine Continuous Power (COP)kW1395 
Fan Quantity 
Fan Reduction kW55.0 
Single Fan Reduction kW55.0 
All Fans ReductionkW55.0 
Engine Net Standby Output  ( LTP)kW*
Engine Net Prime Output  (PRP)kW1571 
Engine Net  Continuous Output  (COP)kW1340 
BMEP for Standby Output bar*
BMEP for Prime Output bar24.42 
BMEP for Continuous Outputbar20.94 
Typical Generation Standby OutputkVA*
Typical Generation Standby OutputkW*
Typical Generation Prime OutputkVA1875 
Typical Generation Prime OutputkW1500
Typical Generation Continuous OutputkVA1600 
Typical Generation Continuous OutputkW1280
Typical  Alternator Efficiency 95.5%
Voltage of GensetV3300/6600
MECC alte Generator's Model *
MARATHON Generator's Model MXM-1520-4
Coupler Model ZL8-01
Power Factor 0.8
Speed droop (static) elect. Gov. 0-5%
Governing standards to ISO 8528 Parts 1 and 5 G3
Max. step load acceptance, 1st step ( % Prime Output ) 37%
Basic Performance Datasheet  
Aspiration Type Turbocharger, air-water aftercooler
Injection Type Direct Injection
Configuration Vee
No. of Cylinders 12
Displacement l53.1
Bore mm170
Stroke mm195
Compression Ratio 13.5:1/14:1
Piston Speed m/s9.75
Rotation Direction (from flywheel) Counter Clockwise
Number of Flywheel Teeth  218 
Flywheel House Size SAE00-21
Lubrication System  
Lube Oil Specification API-CF4
Oil Capacity l180
Max. Permissible Oil Temperature °C110
Oil Pressure Warning kPa300 
Oil Pressure Shutdown kPa200 
Cooling System  
Coolant Capacity for Engine l100
Max. Permissible Temperature  °C90
Max. Coolant Warning Temperature  °C95
Max. Coolant Shutdown Temperature  °C98
Thermostat Open Temperature °C71
Radiator Cooling Flow  m³/min2750
Flow of Cylinder liner Coolant pump m³/h48
Flow of aftercooler Coolant pump m³/h45
Heat dissipation (engine radiator)  kW566 
Heat dissipation (CAC)  kW382
Heat dissipation (convection)kW97
Mode of Radiator(cooper core , 40 C  environment's temp ) 6300080
Fuel System  
Governor Type Electrical 
Engine Output at genset prime outputkW1626 
Fuel Consumption at 25% of  genset prime outputl/h118.34 
Fuel Consumption at 50% of genset prime outputl/h204.04 
Fuel Consumption at 75% of genset prime outputl/h281.02 
Fuel Consumption at 100% ofgenset prime outputl/h370.99 
Lowest Fuel Consumption Ratiog/kW.hr190.55 
Intake & Exhaust System ( On Standby Output )  
Combustion Air Consumption m³/min173.47 
Max. Intake Restriction KPa2
Exhaust Temperature (Before Turbo)°C600
Exhaust Temperature (After Turbo)°C480
Max. Exhaust Back Pressure KPa2
Exhaust Gas Flow  m³/min435.03 
Exhaust Flange Diameter mm2*250
Electrical System  
Charging Alternator Voltage V28
Charging Alternator Capacity A55
Starting VoltageV24
Starting Motor Capacity kW13
Minimum Battery Capacity Ah4*200
Quantity of generator set's Bearing  (( For 400-660VAC generator ) 1
Quantity of generator set's Bearing  (( For Above 3300VAC generator ) 2
Engine Dimension  
Length mm3096
Width mm1459
Height mm1820
Engine Dry Weight w/o Cooling Systemkg5200

1500kw High Voltage 3kv 6kv Diesel Generator with Marathon Alternator
1500kw High Voltage 3kv 6kv Diesel Generator with Marathon Alternator
1500kw High Voltage 3kv 6kv Diesel Generator with Marathon Alternator
1500kw High Voltage 3kv 6kv Diesel Generator with Marathon Alternator
For more products, please visit our showroom honnydg.en.made-in-china.com

 
Genset ModelPrime Power
 
kW/kVA )
Standby Power
 
kW/kVA )
Fuel Consumption
l/h )
Engine ModelVoltage LevelDimension
mm )
Weight
kg )
HGM825HV11600/750660/825162PTAA1340G56.3/6.6/10/10.5/11kV5000x1780x21005800
HGM1000HV11720/900800/1000194PTAA1780G56.3/6.6/10/10.5/11kV5000x1780x21006500
HGM1100HV11800/1000880/1100211PTAA1780G76.3/6.6/10/10.5/11kV5200x2190x24008800
HGM1375HV111000/12501100/1375258PTAA37EG36.3/6.6/10/10.5/11kV5200x2190x24009500
HGM1650HV111200/15001320/1650309QTA3240G56.3/6.6/10/10.5/11kV5800x2190x260012000
HGM1875HV111350/1687.51500/1875347QTA3240G76.3/6.6/10/10.5/11kV5800x2190x260012000
HGM2063HV111500/18751650/2063386QTA3240G96.3/6.6/10/10.5/11kV5800x2190x260013500
HGM2200HV111600/20001760/2200414QTA4320G36.3/6.6/10/10.5/11kV6500x2600x260015500
HGM2500HV111800/22502000/2500464QTA4320G56.3/6.6/10/10.5/11kV7000x2600x295016500
HGM2750HV112000/25002200/2750515QTA4320G76.3/6.6/10/10.5/11kV7000x2600x315019500
HGM2752HV112000/25002200/2750521QTA5400G16.3/6.6/10/10.5/11kV8300x2600x355019500
HGM3025HV112200/27502420/3025567QTA5400G36.3/6.6/10/10.5/11kV8300x2600x355020500
HGM3300HV112400/30002640/3300619QTA5400G56.3/6.6/10/10.5/11kV8300x2600x355022500

NOTE:
1. Voltage can be designed by customer for 3kV, 6kV, 10kV system and adjustable.
2. Rating Frequency 50Hz, 1500rpm, P.F. 0.8.
3. Environment Condition: 1000 meter altitude, 40 ºC temperature.
4. All above parameters are only for reference. If any change, no notify separately.